Introduction
PROFIBUS is not one communication system, but a variety of protocols built on the same field-bus technology bundle. Users can combine varieties of PROFIBUS protocols with their own software and other requirements, resulting in a unique application profile. With many profiles available, PROFIBUS can suit specific needs. One thing remains the same, though. Through thorough testing, PROFIBUS devices meet a high standard of quality befitting a high quality network
PROFIBUS is not one communication system, but a variety of protocols built on the same field-bus technology bundle. Users can combine varieties of PROFIBUS protocols with their own software and other requirements, resulting in a unique application profile. With many profiles available, PROFIBUS can suit specific needs. One thing remains the same, though. Through thorough testing, PROFIBUS devices meet a high standard of quality befitting a high quality network
PROFIBUS networks make use of three separate layers of the
OSI Network model. First, PROFIBUS describes the application layer. There are
multiple versions of PROFIBUS that handle different types of messaging at the
application layer. Some of the types of messaging PROFIBUS supports include
cyclic and acyclic data exchange, diagnosis, alarm-handling, and isochronous
messaging.
PROFIBUS does not define layers three through six. It does, however, define the data link and physical layers, layers one and two. The data link layer is completed through a Field bus Data Link, or FDL. The FDL system combines two common schemes, master-slave methodology and token passing. In a master-slave network, masters, usually controllers, send requests to slaves, sensors and actuators. The slaves respond accordingly. PROFIBUS also includes token passing, a system in which a “token” signal is passed between nodes. Only the node with the token can communicate. The token passing concept is like the speaking conch; only the person with the conch is allowed to talk.
Finally, PROFIBUS defines a physical layer, though it leaves room for flexibility. PROFIBUS systems can have three types of media. The first is a standard twisted-pair wiring system, in this case RS485. Two more advanced systems are also available. PROFIBUS systems can now operate using fiber-optic transmission in cases where that is more appropriate. A safety-enhanced system called Manchester Bus Power, or MBP, is also available in situations where the chemical environment is prone to explosion.
PROFIBUS does not define layers three through six. It does, however, define the data link and physical layers, layers one and two. The data link layer is completed through a Field bus Data Link, or FDL. The FDL system combines two common schemes, master-slave methodology and token passing. In a master-slave network, masters, usually controllers, send requests to slaves, sensors and actuators. The slaves respond accordingly. PROFIBUS also includes token passing, a system in which a “token” signal is passed between nodes. Only the node with the token can communicate. The token passing concept is like the speaking conch; only the person with the conch is allowed to talk.
Finally, PROFIBUS defines a physical layer, though it leaves room for flexibility. PROFIBUS systems can have three types of media. The first is a standard twisted-pair wiring system, in this case RS485. Two more advanced systems are also available. PROFIBUS systems can now operate using fiber-optic transmission in cases where that is more appropriate. A safety-enhanced system called Manchester Bus Power, or MBP, is also available in situations where the chemical environment is prone to explosion.
Topology
PROFIBUS uses the bus topology. In this topology, a central line, or bus, is wired throughout the system. Devices are attached to this central bus. One bus eliminates the need for a full-length line going from the central controller to each individual device.
In the past, each PROFIBUS device had to connect directly to the central bus. Technological advancements, however, have made it possible for a new “two-wire” system. In this topology, the PROFIBUS central bus can connect to a ProfiNet Ethernet system. In this way, multiple PROFIBUS busses can connect to each other.
Types of PROFIBUS
PROFIBUS has advanced through a handful of revisions. In some cases, advances have led to a new type of PROFIBUS. In other cases, new revisions mean different versions of the same type of PROFIBUS. In any case, the variety of PROFIBUS solutions mean the system can be adapted to fit the varying needs of different industries.
PROFIBUS uses the bus topology. In this topology, a central line, or bus, is wired throughout the system. Devices are attached to this central bus. One bus eliminates the need for a full-length line going from the central controller to each individual device.
In the past, each PROFIBUS device had to connect directly to the central bus. Technological advancements, however, have made it possible for a new “two-wire” system. In this topology, the PROFIBUS central bus can connect to a ProfiNet Ethernet system. In this way, multiple PROFIBUS busses can connect to each other.
Types of PROFIBUS
PROFIBUS has advanced through a handful of revisions. In some cases, advances have led to a new type of PROFIBUS. In other cases, new revisions mean different versions of the same type of PROFIBUS. In any case, the variety of PROFIBUS solutions mean the system can be adapted to fit the varying needs of different industries.
PROFIBUS FMS
The initial version of PROFIBUS was PROFIBUS FMS, Fieldbus Message Specification. PROFIBUS FMS was designed to communicate between Programmable Controllers and PCs, sending complex information between them. Unfortunately, being the initial effort of PROFIBUS designers, the FMS technology was not as flexible as needed. This protocol was not appropriate for less complex messages or communication on a wider, more complicated network. New types of PROFIBUS would satisfy those needs. PROFIBUS FMS is still in use today, though the vast majority of users find newer solutions to be more appropriate.
PROFIBUS DP
The second type of PROFIBUS is more universal. Called PROFIBUS DP, for Decentralized Periphery, this new protocol is much simpler and faster. PROFIBUS DP is used in the overwhelming majority of PROFIBUS application profiles in use today. Application profiles allow users to combine their requirements for a specific solution, and they will be discussed in more detail shortly.
PROFIBUS DP has, itself, three separate versions. Each version, from DP-V0 to DP-V1 and DP-V2, provides newer, more complicated features.
The initial version of PROFIBUS was PROFIBUS FMS, Fieldbus Message Specification. PROFIBUS FMS was designed to communicate between Programmable Controllers and PCs, sending complex information between them. Unfortunately, being the initial effort of PROFIBUS designers, the FMS technology was not as flexible as needed. This protocol was not appropriate for less complex messages or communication on a wider, more complicated network. New types of PROFIBUS would satisfy those needs. PROFIBUS FMS is still in use today, though the vast majority of users find newer solutions to be more appropriate.
PROFIBUS DP
The second type of PROFIBUS is more universal. Called PROFIBUS DP, for Decentralized Periphery, this new protocol is much simpler and faster. PROFIBUS DP is used in the overwhelming majority of PROFIBUS application profiles in use today. Application profiles allow users to combine their requirements for a specific solution, and they will be discussed in more detail shortly.
PROFIBUS DP has, itself, three separate versions. Each version, from DP-V0 to DP-V1 and DP-V2, provides newer, more complicated features.
PROFIBUS PA
PROFIBUS PA is a protocol designed for Process Automation. In actuality, PROFIBUS PA is a type of PROFIBUS DP Application profile. PROFIBUS PA standardizes the process of transmitting measured data. It does hold a very important unique characteristic, though. PROFIBUS PA was designed specifically for use in hazardous environments.
In most environments, PROFIBUS PA operates over RS485 twisted pair media. This media, along with the PA application profile supports power over the bus. In explosive environments, though, that power can lead to sparks that induce explosions. To handle this, PROFIBUS PA can be used with Manchester Bus Powered technology (MBP).
MBP Technology
The MBP media was designed specifically to be used in PROFIBUS PA. It permits transmission of both data and power. The technology steps the power down, though. A smaller power reduces, or nearly eliminates, the possibility of explosion. Buses using MBP can reach 1900 meters and can support branches. Application Profiles
PROFIBUS can be tailored to specific needs using application profiles. There are many profiles that combine standards for transmission media, communication protocol (FMS, DP-V0, etc…), and unique protocols. Each application profile is tailored to a specific use, and new profiles appear regularly. To list them all would be cumbersome.
PROFIBUS PA is a protocol designed for Process Automation. In actuality, PROFIBUS PA is a type of PROFIBUS DP Application profile. PROFIBUS PA standardizes the process of transmitting measured data. It does hold a very important unique characteristic, though. PROFIBUS PA was designed specifically for use in hazardous environments.
In most environments, PROFIBUS PA operates over RS485 twisted pair media. This media, along with the PA application profile supports power over the bus. In explosive environments, though, that power can lead to sparks that induce explosions. To handle this, PROFIBUS PA can be used with Manchester Bus Powered technology (MBP).
MBP Technology
The MBP media was designed specifically to be used in PROFIBUS PA. It permits transmission of both data and power. The technology steps the power down, though. A smaller power reduces, or nearly eliminates, the possibility of explosion. Buses using MBP can reach 1900 meters and can support branches. Application Profiles
PROFIBUS can be tailored to specific needs using application profiles. There are many profiles that combine standards for transmission media, communication protocol (FMS, DP-V0, etc…), and unique protocols. Each application profile is tailored to a specific use, and new profiles appear regularly. To list them all would be cumbersome.
Some application profiles are widespread, though. Two
examples are PROFIsafe and PROFIdrive. PROFIsafe
PROFIsafe uses additional software to create a high-integrity network. This network is useful in situations where high safety is a requirement. For suppliers and manufacturers to be certified in PROFIsafe, they must maintain high standards in quality.
PROFIdrive
PROFIdrive was created for motion control applications. Software added to the PROFIBUS DP specification allows the network to achieve precise control of servo motors and other equipment. Thus PROFIdrive can achieve synchronization across the network.
PROFIsafe uses additional software to create a high-integrity network. This network is useful in situations where high safety is a requirement. For suppliers and manufacturers to be certified in PROFIsafe, they must maintain high standards in quality.
PROFIdrive
PROFIdrive was created for motion control applications. Software added to the PROFIBUS DP specification allows the network to achieve precise control of servo motors and other equipment. Thus PROFIdrive can achieve synchronization across the network.
Quality Assurance
The PROFIBUS User Organization has created a conformance testing program to ensure devices meet high standards. In this program, a device is sent to an independent laboratory for testing. The device then undergoes a comprehensive series of tests, including Hardware, Conformity, and Function tests, among others. The test results are documented
When a device passes all tests, its manufacturer can apply for a conformance certificate. The certificate is valid for three years and can be renewed with further testing.
The PROFIBUS User Organization has created a conformance testing program to ensure devices meet high standards. In this program, a device is sent to an independent laboratory for testing. The device then undergoes a comprehensive series of tests, including Hardware, Conformity, and Function tests, among others. The test results are documented
When a device passes all tests, its manufacturer can apply for a conformance certificate. The certificate is valid for three years and can be renewed with further testing.